Step 4 After setting teamwork control parameters, choose Monitoring > Air Conditioner >
NetCol5000-A0101 > Running Info > Teamwork Information and check that the displayed
teamwork control information is consistent with the parameter settings.
If the information displayed under Teamwork Information is inconsistent with the parameter
settings, check the teamwork control cable connection and teamwork control parameter
settings.
----End
6.4.2.3 Setting Max Speed of Indoor Fan
If the equipment room is near a noise-sensitive place, such as an office or a meeting room,
limit the rotational speed of the indoor fan within 80% to lower the noise.
Procedure
Step 1 Choose Monitoring > Air Conditioner > NetCol5000-A0101 > Running Parameters >
Indoor Fan Parameters, set Max speed of indoor fan to 80%.
Step 2 Set Max speed of indoor fan to 80% of other smart cooling products in turn.
----End
6.4.3 Commissioning
Prerequisites
Check that the indoor and outdoor units have been powered on.
Before starting the compressor, ensure that the electric heating belt of the crankcase has been
preheated for more than 12 hours.
The one-way indoor unit pipe is longer than 30 meters but not greater than 60 meters.
Therefore you need to add refrigerant during commissioning.
Before charging refrigerant, ensure that air is exhausted from the gas pipe connecting to
the refrigerant cylinder.