5.6.1 Resetting the safety functions to the factory setting
Procedure
1. Go online.
2. Select "Commissioning".
3. Select "Backing up/reset".
4. Select "Safety parameters are reset".
5. Press the "Start" button.
6. Enter the password for the safety functions.
7. Con󹪝rm that the parameters have been saved (RAM to ROM).
8. Go o󹪠ine.
9. Switch o󹪜 the converter power supply.
10.Wait until all LEDs on the converter are dark.
11.Switch on the converter power supply again.
You have restored the safety functions in the converter to the factory settings.
Exception: The password for the safety functions is not reset.
Password (Page258)
Procedure with an operator panel
1. Set p0010 = 30
Activate reset settings.
2. p9761 = …
Enter the password for the safety functions
3. Start the reset with p0970=5.
4. Wait until the converter sets p0970 = 0.
5. Set p0971=1.
6. Wait until the converter sets p0971 = 0.
Commissioning
5.6Restoring the factory setting
SINAMICS G120C Converters
154 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK

Table of Contents

Other manuals for Siemens SINAMICS G120C DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C DP and is the answer not in the manual?

Siemens SINAMICS G120C DP Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G120C DP
CategoryInverter
LanguageEnglish

Related product manuals