Suppressing the automatic restart only functions for the setting p1210=6, 16 or 26.
Note
Motor starts in spite of an OFF command via the eldbus
The converter responds with a fault if eldbus communication is interrupted. For one of the
settings p1210 = 6, 16 or 26, the converter automatically acknowledges the fault and the motor
restarts, even if the higher-level control attempts to send an OFF command to the converter.
• In order to prevent the motor automatically starting when the eldbus communication fails,
you must enter the fault number of the communication error in parameter p1206.
Parameter
Number Name Factory setting
p1206 Automatic restart faults not active 0
p1210 Automatic restart mode 0
p1211 Automatic restart, start attempts 3
p1212 Automatic restart, wait time start attempts 1s
p1213[0] Automatic restart monitoring time
for restart
60s
p1213[1] Reset automatic restart monitoring time for
startup counter
0s
8.30 Kinetic buering (Vdc min control)
Overview
Kinetic buering increases the drive availability. The kinetic buering utilizes the kinetic
energy of the load to buer line dips and failures. During a line dip, the converter keeps the
motor in the switched-on state for as long as possible. One second is a typical maximum
buer time.
Requirement
The following requirements must be fullled to practically use the "kinetic buering" function:
• The driven machine has a suciently high inertia.
• The application allows a motor to be braked when the line supply fails.
Advanced commissioning
8.30Kinetic buering (Vdc min control)
SINAMICS G120C Converters
350 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK