A.1.3 Firmware version 4.7 SP10
Table A-3 New functions and function changes in rmware4.7 SP10
Function SINAMICS
G120 G120D
1 New parameter r7844 [1] for displaying the rmware version in plain text.
"04070901" is equivalent to rmware version V4.7 SP9 HF1, for example
✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
2 Modbus RTU:
• The factory setting of parameter p2040 was increased to provide more
robust converter operation. Monitoring time for data failure at the Mod‐
bus interface: p2040=10s
• r2057 indicates how the address switch on the converter is set
✓ ✓ ✓ ✓ ✓ ✓ - - -
3 BACnet MS/TP:
• New factory setting for more robust converter operation:
– Baud rate p2020=38.4kBd
– Monitoring time for data failure at the BACnet interface was in‐
creased: p2040=10s
– Factory setting for the maximum number of info frames p2025 [1] = 5
– Factory setting for the maximum number of manager addresses
p2025 [3]=32
• r2057 indicates how the address switch on the converter is set
- - ✓ - - - - - -
4 Further technological unit kg/cm² for unit switchover ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
5 Further technological unit kg/cm² for additional technology controllers - - ✓ - - - - - -
Appendix
A.1New and extended functions
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 451