6. Select menu "Parameter".
0HQX
3DUDPHWHUV6HWXS'LDJQRVWLFV
8S
'RZQORDG
([WUDV6XSSRUW
3DUDPHWHUV
Parameter groups
Search by number
My parameters
Changed parameters
Parameter filter
7. To start commissioning of the safety functions, set p10 = 95.
8. Enter the password for the safety functions in p9761.
9. To conrm the settings of the safety functions, set p9701 = AC.
10.To exit commissioning of the safety functions, set p10 = 0.
11.Back up the settings so that they are protected against power failure.
0HQX
3DUDPHWHUV6HWXS'LDJQRVWLFV
8S
'RZQORDG
([WUDV6XSSRUW
([WUDV
'ULYHIDFWRU\UHVHW
6DIHIDFWRU\UHVHW
'HIDXOWGDWDVHW
3DUDPHWHUVDYLQJPRGH
6DYH5$0WR520
6WDWXVVFUHHQZL]DUG
'ULYHLGHQWLW\
3DUDPHWHUVHWWLQJV
3DQHOVHWWLQJV
12.Switch o the converter power supply.
13.Wait until all LEDs on the converter are dark.
14.Switch on the converter power supply again.
15.Perform a reduced acceptance test.
Reduced acceptance after component replacement and rmware change (Page417)
You have replaced the converter and transferred the safety function settings from the
operator panel to the new converter.
❒
10.2.2.5 Download from Smart Access
Overview
You can transfer the converter settings that are backed up on the digital terminal device back
into the converter.
Corrective maintenance
10.2Downloading the converter settings
SINAMICS G120C Converters
396 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK