Frequency limits Factory See
Parameter name Adjusting range default page
A061
Frequency upper limit 0,00...400,0 Hz 0,00 Hz 29
A062
Frequency lower limit 0,00...400,0 Hz 0,00 Hz 29
A063
1st Jump frequency 0,00...400,0 Hz 0,00 Hz 30
A064
1st Jump frequency width 0,00...10,0 Hz 0,50 Hz 30
A065
2nd Jump frequency 0,00...400,0 Hz 0,00 Hz 30
A066
2nd Jump frequency width 0,00...10,0 Hz 0,50 Hz 30
A067
3rd Jump frequency 0,00...400,0 Hz 0,00 Hz 30
A068
3rd Jump frequency width 0,00...10,0 Hz 0,50 Hz 30
PID Configuration Factory See
Parameter name Adjusting range default page
A071
Selection of PID function: ON/OFF 00 or 01 00 32
A072
PID controller: Proportional gain (kp) 0,2...5,0 1,0 32
A073
PID controller: Integral gain(Tn) 0,0...3600 s 1,0 32
A074
PID controller: Differential gain(Tv) 0,00...100,0 s 0,00 32
A075
PID controller: Scale conversion 0,01...99,99 1,00 33
A076
PID controller: Feedback destination 00 or 01 00 33
C044
PID controller: Level of deviation 0...100 % 3,0 % 33
Automatic voltage regulation Factory See
Parameter name Adjusting range default page
A081
Selection of AVR function 00 to 02 02 34
A082
Selection of voltage for AVR 380...480 V 400 V 34
Ramp adjustment Factory See
Parameter name Adjusting range default page
A092
2nd Acceleration ramp 0,01...3600 s 15,00 s 34
A093
2nd deceleration ramp 0,01...3600 s 15,00 s 34
A094
Select method of 2nd stage 00 or 01 00 34
A095
Switch-over 1./2. acceleration ramp 0,00...400,0 Hz 0,00 Hz 35
A096
Switch-over 1./2. deceleration ramp 0,00...400,0 Hz 0,00 Hz 35
A097
Pattern of acceleration ramp 00 to 03 00 35
A098
Pattern of deceleration ramp 00 to 03 00 35
A131
Acceleration curve constant 01 to 10 02 35
A132
Deceleration curve constant 01 to 10 02 35
b091
Stopping mode selection 00 or 01 00 35
A069
Acceleration stop frequency 0,00...400,0 Hz 0,00 Hz 35
A070