120 Fault tracing
Controller warnings
Code Warning Cause What to do
40006 Attempt to configure too
many axes
(_ecTOO_MANY_AXES)
The device configuration file
has attempted to assign
more axes than are
available on the controller.
Re-run the System Configuration Wizard .
40007 CamBox segments have
been skipped
(_ecCAM_BOX_OVERRUN)
The cam box has skipped a
segment. This can happen
if the source is moving fast
enough to cause a
segment to be skipped.
See CAMBOX in Mint WorkBench Help,
look at "position_array". Either slow down
the source or increase the size of the
segments
40012 A host event has failed with
retries
(_ecEVENT_RETRY_WAR
NING)
A host (i.e. ActiveX) event
handler has failed to
acknowledge an event that
has been raised by the
controller. There is a 'time-
out' period of 1 second in
which the host must
acknowledge an event.
If the host does not acknowledge the event
after 3 time-out periods, the controller
generates warning 40012. See ERRDATA
for details of the error.
40013 Attempted to assign too
many servo axes
(_ecTOO_MANY_SERVO_
AXES)
During the processing of the
..CMCF / .DCF (device
configuration file), too many
servo axes were configured.
To fix this issue, use the System Config
Wizard to reduce the number of configured
servo axes.
40014 Attempted to assign too
many stepper axes
(_ecTOO_MANY_STEPPER
_AXES)
During the processing of the
..CMCF / .DCF (device
configuration file), too many
stepper axes were
configured.
To fix this issue, use the System Config
Wizard to reduce the number of configured
stepper axes.
40015 Attempted to assign too
many virtual axes
(_ecTOO_MANY_VIRTUAL
_AXES)
During the processing of the
..CMCF / .DCF (device
configuration file), too many
virtual axes were
configured.
To fix this issue, use the System Config
Wizard to reduce the number of configured
virtual axes.
40016 Attempted to assign too
many remote axes
(_ecTOO_MANY_REMOTE
_AXES)
During the processing of the
..CMCF / .DCF (device
configuration file), too many
remote axes were
configured.
To fix this issue, use the System Config
Wizard to reduce the number of configured
remote axes.
40021 All controller warnings
cleared
(_ecCONTROLLER_WARNI
NGS_CLEARED)
This information message
can appear in the error log
to indicate that all controller
warnings have been
cleared.
No Action Required
40022 Last reset was not controlled
(_ecRESET_NOT_CONTR
OLLED)
Last reset was not
controlled
To fix this issue, use the System Config
Wizard to reduce the number of configured
servo axes.

Table of Contents

Other manuals for ABB MicroFlex e190

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB MicroFlex e190 and is the answer not in the manual?

ABB MicroFlex e190 Specifications

General IconGeneral
BrandABB
ModelMicroFlex e190
CategoryServo Drives
LanguageEnglish

Related product manuals