PTS PRESSURE TRANSMITTER
CALIBRATION
E - 5
Figure E-2. Calibration Flowchart (PTS)
Key Display Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES.
Select BENCH CALIB.
If the transmitter is configured for digital operation,
the D-TO-A ADJUST selection would not appear.
T01340A
DIGITAL
ANALOG
CALIBRATION
COMPLETE
BENCH
REZERO
ENTER LOW
CALIBRATION
PRESSURE
D-TO-A
CAL
METHOD
CAL
METHOD
ARROW
KEYS
ARROW
KEYS
METER VALUE
ENTRY
METER VALUE
ENTRY
ADJUST
OUTPUT
TO 4 mA
ADJUST
OUTPUT
TO 4 mA
ADJUST
OUTPUT
TO 20 mA
ADJUST
OUTPUT
TO 20 mA
4 mA
CALIBRATION
ENTER METER
VALUE 4.000
4 mA
CALIBRATION
ENTER METER
VALUE 4.000
20 mA
CALIBRATION
ENTER METER
VALUE 20.000
20 mA
CALIBRATION
ENTER METER
VALUE 20.000
EQUALIZE
PRESSURE
ENTER HIGH
CALIBRATION
PRESSURE
REZERO
COMPLETE
APPLY LOW
CALIBRATION
PRESSURE
C
A
L
I
B
R
A
T
E
APPLY HIGH
CALIBRATION
PRESSURE
CALI-
BRATE
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→ YES
ENTER
CALIBRATION
D-TO-A ADJUST
→ BENCH CALIB.
REZERO