Input definition – type Area
(INPUT/OUTPUT, 1, )
INPUT DEFINITION State :false
Input :1 Trig. :latched
Type :Area Mode :active
Area :1 continuous
Fct. :Fire Event unlogged
0. .9, ^V, <>, E, X
Alarms: 0 Faults: 0 Cond.: 0 P: 1 SDZ
Return to Input/Output Menu Page 109
Place cursor at TYPE
Select Type: AREA and press (Unlock memory!)
Select the Function
*See Common Facilities - All Input Types, Page 111 for description of Input, State,
Trigger, Mode, Event and Text
An area is defined as a group of zones (see Page 99). An input can be assigned to an
area by specifying the area number and the function.
List of Functions:
Fire
Fault
Coincidence
Condition
Disable
Pre Warning
-
An area coincidence is two or more zones allocated to the area in a fire alarm condition.
It is independent of zones in coincidence. *See Page 99
Trigger: Latched/Unlatched
Mode: Passive/Active
Always continuous
Event: Always unlogged
Text: Not applicable
* See Input Description in the Serial Communication Format

Table of Contents

Other manuals for Aritech FP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech FP2000 Series and is the answer not in the manual?

Aritech FP2000 Series Specifications

General IconGeneral
BrandAritech
ModelFP2000 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals