Output delays
(SET TIMES MENU, 2, )
OUTPUT DELAYS
Sounder :120 s Delay :off
Fbrig :120 s Delay :off
Fltrt :0 s Delay :off
Fprot :0 s Delay :off
0. . 9, ^V, <>, E, X
Alarms: 0 Faults: 1 Cond.: 0 P: 1 FDZ
Return to Set Times Menu Page 68
Select item to be changed
or 0..9 change data in item (Unlock memory!)
Confirm change
This menu allows the setting of the delay before activation of the Sounder, Fire Brigade,
Fire Protection and Fault Routing output relays.
The Sounder and Fire Brigade Delays are enabled from the front panel of the FP2000 fire
panel. Switching the Sounder or Fire Brigade Delay OFF during the delay time will cancel
the delay and operate the required output immediately.
The delays can be set from 0 to 600 seconds.
Fire protection and Fault routing delays are fixed at zero (0) seconds.