Memory allocation 1
(CONFIGURATION, 2, )
MEMORY ALLOCATION Free unlocked :175238
Free locked :84042
Logic :600 Input Text :40
Inputs :200 Output Text :40
Outputs :200 Zone Text :40
Events :999 Area Text :40
more 0. .9, ^V, <>, E, X
Alarms: 0 Faults: 0 Cond.: 0 P: 1 SDZ
Return to Configuration Menu Page 26
Select item to be changed
or 0..9 change data in item (Unlock memory!)
Confirm change
Press [More ] to view Memory Allocation 2 Page 34
-
Changing memory allocation will clear all existing programmed data from memory!
The user must reprogram all site data after changing any items in memory allocation.
The random access memory (RAM) of the fire panel is partitioned for different types of
data. Some of this data is contained within locked memory; other data is in unlocked
memory.
The default memory allocation for the FP2000 is shown. Further information is obtained
by using [More ] (Page 34). The default memory allocation should be correct for most
applications and should only be changed if the user has particular requirements that
exceed the parameters given.
The amount of free locked and unlocked memory is dynamically displayed on the screen
as allocations are increased or decreased.
!
When exiting from this menu, the user is prompted as to whether the allocation is to be
saved or not. This prompt will occur even if no parameters have been changed. If the
allocation is saved then all RAM is cleared and the fire panel must be reprogrammed.
Press for no save
Press for YES and then in order to save the allocation (Unlock memory!)

Table of Contents

Other manuals for Aritech FP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech FP2000 Series and is the answer not in the manual?

Aritech FP2000 Series Specifications

General IconGeneral
BrandAritech
ModelFP2000 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals