Input definition – type Adjacent Area
(INPUT/OUTPUT, 1, )
INPUT DEFINITION State :false
Input :1 Trig. :latched
Type :Adj. Area Mode :active
Area :1 continuous
Fct. :Fire Event unlogged
0. .9, ^V, <>, E, X
Alarms: 0 Faults: 0 Cond.: 0 P: 1 SDZ
Return to Input/Output Menu Page 109
Place cursor at TYPE
Select Type: ADJ AREA and press (Unlock memory!)
Select the Function
*See Common Facilities - All Input Types, Page 111 for description of Input, State,
Trigger, Mode, Event and Text
Adjacent areas are assigned to areas using the Area Setup Menu, Page 99. An input can
be activated by an adjacent area by specifying the area number and function. Adjacent
areas have significance in PA evacuation systems where an area in fire is evacuated and
the adjacent areas have warning alarms.
List of Functions:
Fire
Fault
Coincidence
Condition
Disable
Pre Warning
The adjacent areas of the specified area will activate the input.
Trigger: Latched/Unlatched
Mode: Passive/Active
Always continuous
Event: Always unlogged
Text: Not applicable
* See Input Description in the Serial Communication Format