(SYSTEM MENU, 3, )
CLEAR SITE DATA
1 Devices 2 Zones
3 Areas 4 Inputs
5 Outputs 6 System
7 Loops 8 Logic Table
more 0. . 9, <>, E, X
Alarms: 0 Faults: 1 Cond.: 0 P: 1 SDZ
Select number or use and press (Unlock memory!)
When prompted for confirmation:
For Devices select loop number or use and press
All other selections use for YES and press
Return to System Menu Page 25
*See also Set Default, Page 65
All or parts of the RAM memory can be cleared of data. Certain data is also pre-set as
shown below. The data blocks that can be cleared (initialised) are:
1 Devices – Select the loop number (for all loops)
The devices of the selected loop(s) are set to:
Status: Disabled
Type: None
Zone: Ø
Day level: 3
Soak test: Disabled
Test value: Ø
Contamination: Ø
Statistics: Cleared
2 Zones – All zones are set to:
Status: Enabled
Mode: Normal
Area: 0
Safe Zone: Disabled
On/Off: Disabled
Day/Night: Disabled
Sounder Delay: Disabled
Fire Brigade Delay: Disabled
3 Areas – All areas are set to:
Status: Enabled
Coincidence: Unlogged
Adjacent area 1-5: Ø
4 Inputs – All inputs are set to:
Type: None

Table of Contents

Other manuals for Aritech FP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech FP2000 Series and is the answer not in the manual?

Aritech FP2000 Series Specifications

General IconGeneral
BrandAritech
ModelFP2000 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals