Clear device statistics
(MAINTENANCE MENU, 2, )
CLEAR DEVICE STATISTICS
Enter Zone Nr. (0 for all) :1
0. .9, ^V, <>, E, X
Alarms: 0 Faults: 0 Cond.: 0 P: 1 SDZ
Return to Maintenance Menu Page 157
Enter 0..9 or to select zone. 0 selects all zones
Confirm entry
*See Device Statistics, Page 83
To clear an individual device, see Page 83
The statistics of the devices on a zone will be cleared and set to default values. Selecting
zone Ø will clear all devices.
The values that are affected are:
FldAvg: set to 50
Alarms: set to 0
High: set to 0
Low: set to 255
Contam: set to 0
Communication Quality: set to 0
The test value of the device is not affected.