Fast Compensation
(MAINTENANCE MENU, 7, )
Returns Automatically to Maintenance Menu Page 157
This function will allow the panel to use a fast compensation algorithm to compensate
quickly according to the current analogue values of the smoke detectors. It may be
particularly useful in the event of clearing all device statistics when there may already be
devices that are highly compensated. With no compensation applied, these devices may
be very sensitive and prone to nuisance alarms.