Standard I/O facilities
• Rugged loop driver optimised for
− EMC/EMI regulations
− Operation in worst case conditions of high capacitance and resistance which
makes it ideal for retrofit market.
• Current loop to drive up to 15 fireman’s panels
• 4x Programmable inputs and 1x Supervised input
• 4x Programmable relays
• Monitored alarm bell, fire brigade, fire protection and fault routing
• 3x Supervised inputs for fire brigade feedback, fire protection fault and fault routing
fault.
• Dual RS232 ports assigned to text, graphics, external printer or modem.
Mechanical data
Dimensions H W D
16/64 Zone Cabinet 609 441 109
64/255 Zone Cabinet 804 441 109
Mass (without batteries)
16/64 Zone Cabinet 11kg
64/255 Zone Cabinet 15kg