Output definition – type Event
(INPUT/OUTPUT, 2, )
OUTPUT DEFINITION State :false
Output :1 Trig. :latched
Type :Event Mode :normal
continuous
unlogged
Numeric A. .z, ^V, <>, E, X
Alarms: 0 Faults: 0 Cond.: 0 P: 1 SDZ
Return to Input/Output Menu Page 109
Select Type: EVENT and press
Enter text
Select Trigger and Event
The output, when switched true by logic is logged to the event buffer.
In addition, logged as fire will create a common fire alarm; logged as fault will create a
common fault warning; logged as condition will create a common condition.
Logged as fire, fault or condition causes the Output event to be displayed in the alarm
screens.
Trigger: Latched/unlatched
Mode: Normal only
Continuous only
Unlogged/logged/fire/fault/condition
Text: Allowed
* See Output Description in the Serial Communication Format