System Setup
(SYSTEM MENU, 5, )
SYSTEM SETUP
Fbrig : continuous FSK Heater : off
FBF : none
Language : English
Operation : EN
Protocol : Aritech 900
^v, <>, E, X
Alarms: 0 Faults: 0 Cond.: 0 P: 1 SDZ
Return to Configuration Menu Page 26
Select field to be changed
Select mode
Confirm entry (Unlock memory!)
Fbrig:
The Fbrig function can only be assigned to a firepanel with a VdS2000 German Sounder
board with a connected Hauptmelder.
continuous – one continuous pulse is send to the hauptmelder to check its status
pulse – every three seconds a pulse of one second is transmitted to the hauptmelder to
check its status
none – no hauptmelder is connected to the firepanel
FBF:
The FBF function can only be assigned to a firepanel with a VdS2000 German Sounder
board with a connected Bedienfeld to it. The types of Bedienfelds which can be
connected to it is the:
FBF 800 Bedienfeld
FBF 800B Berlin Bedienfeld
DIN 2000-00 Bedienfeld
FSK Heater:
The FSK Heater function can only be assigned to a firepanel with a VdS2000 German
Sounder board with a FSK Heater connected to it. The types of FSK Heaters which can
be connected are:
FSK700 (Note: Needs to be modified to work from 24V)
FSK800
Language:
The operating language of the firepanel is set here. This applies only to the FP11xx/12xx
range of products. The FP2xxx range of products language is set by the dip switch
situated on the host power supply (*See Appendix A of the FP2000 Installation and
Commissioning Manual for dip switch settings as well as languages).
The switch is read at restart, and cannot be changed during operation.
Operation:
The mode of operation of the firepanel is set here. This applies only to the FP11xx/12xx