Access codes
(ACCESS MENU, 1, )
ACCESS CODES
Access No. :1
Access Code :1
Access Level :1
0. . 9, ^V, <>, E, X
Alarms: 0 Faults: 1 Cond.: 0 P: 1 FDZ
Return to Access Menu Page 59
Select item to be changed
or 0..9 change data in item (Unlock memory!)
Confirm entry
*See also Page 61
Six access codes are allowed in order to use the menu screens viz. Access No 1 to
Access No 6. Each of these access numbers can be assigned a numeric code of 1-4
digits. Each access number 1-6 is also allocated an access level: 1-Low level; 2-High
level; Ø-No access.
The access number of the entry code used to gain access to the menus is logged in the
event buffer. After 3 unsuccessful attempts to gain access, an Access Fault message is
given.
Each menu screen of the FP2000 fire panel has an access level. Access numbers that
have an access level 1 cannot use any menus that are set to level 2. In addition, access
codes of level 1 cannot view the access codes of level 2 in this menu (Access Codes).
The message "NO ACCESS" is given in this case.
The default codes and levels are:
Access Number Access Code Access Level
1 1 2
2 2 1
3 3 1
4 4 1
5 5 1
6 6 1