Set default
(SYSTEM MENU, 4, )
SET DEFAULT
1 Devices 2 Zones
3 Area 4 System
5 Loops 6 Configuration
7 Logic table 8 Modem
0. . 9, <>, E, X
Alarms: 0 Faults: 1 Cond.: 0 P: 1 SDZ
Select number or use and press (Unlock memory!)
When prompted for confirmation:
For Devices select loop number or use and press
All other selections use for YES and press
Return to System Menu Page 25
*See also Clear Site Data, Page 62
Certain parameters of the site data can be set to default (predetermined) values. This is a
means of quick-programming the FP2000 fire panel. It is also useful to set default values
to various groups and then selectively change the items that do not correspond to the
default values. Default will only overwrite selected items and will not clear data that is not
affected by the default setting.
In general it is advisable to first clear the selected block using Clear Site Data, and then
set that block to default values.
Default Configuration (see 6 below) will clear all site data from memory and then partition
the memory. This should be done (if required) before any other default operation. (See
Memory Allocation, Page 33.)
The default blocks and their settings are:
1 Devices - Select loop number (Ø for all loops)
Default will only affect devices that are being addressed on the loop(s) at that time
Status: Enabled
Type: Field type
Test value: 255