Goodrive270 series VFD for fan and pump Basic operation guidelines
-141-
1. Enable the multi-pump control function (P94.00=1).
2. Set the variable-frequency motor run mode to fixed (P94.10=0).
3. Set the motor quantity to 4 (P94.11=4).
4. Set RO5–RO8 to control motors A, B, C, and D respectively (set P26.06–P26.09 to 57–60
respectively).
5. Set the contactor closing delay, which is the interval of switchover between the variable-frequency
run mode and power-frequency run mode.
The following figures and tables show the control logic.
PE
N
L1
L2
L3
GD270
M1 M2 M3 M4
QF1
QF2 QF3 QF4
KM1
KM2 KM3 KM4
R S T
U V W
KM1–KM4: Contactors QF1–QF4: Low-voltage breakers
M1–M4: Asynchronous motors
Figure 5-34 Main circuit wiring in fixed variable-frequency run mode
L1/L2/L3
N
RO5 RO6 RO7
RO8
KM1 KM2 KM3
KM4
FR1 FR2 FR3 FR4
Figure 5-35 Control circuit wiring in fixed variable-frequency run mode