Goodrive270 series VFD for fan and pump Function parameter list
-257-
except it is damaged.
If fire mode 2 is selected, the VFD always runs
except it stops upon the following faults: OUT1,
OUT2, OUT3, OC1, OC2, OC3, OV1, OV2,
OV3, and SPO.
Running frequency
in fire mode
0.00Hz–P00.03 (Max. output frequency)
Motor running
direction in fire
mode
0: Run at the default direction.
1: Run at the opposite direction.
0–1
If the fire mode duration reaches 5 minutes, this
flag is set to 1, and no warranty repair is
granted.
Actual month and
date when fire
activated
Actual time when
fire activated
P94 group––HVAC
0: Run at the frequency lower limit
1: Sleep based on running frequency
2: Sleep based on deviation
P00.05–P00.04 (Upper limit of running
frequency)
When the running frequency is less than or
equal to the value and this situation lasts the
time longer than P94.04, sleep is allowed.
0.0–30.0% (relative to PID1 max. value)
When output is positive, if the feedback is
greater than the reference, sleep is allowed only