Goodrive270 series VFD for fan and pump Basic operation guidelines
-73-
Function
code
Name
Description
Default
1: Reserved
Hundreds place: indicates whether to enable
speed-loop integral separation
0: Disable
1: Enable
Thousands place: Reserved
0: Reserved
1: Reserved
P03.36
Speed-loop
differential gain
0.00–10.00s
0.00s
P03.37
High-frequency
current-loop
proportional
coefficient
In the vector control mode (P00.00=3), when the
frequency is lower than the current-loop
high-frequency switching threshold (P03.39), the
current-loop PI parameters are P03.09 and P03.10;
and when the frequency is higher than the current-loop
high-frequency switching threshold, the current-loop PI
parameters are P03.37 and P03.38.
P03.37 setting range: 0–65535
P03.38 setting range: 0–65535
P03.39 setting range: 0.0–100.0% (of the max.
frequency)
1000
P03.38
High-frequency
current-loop
integral
coefficient
1000
P03.39
Current-loop
high-frequency
switching
threshold
100.0%
P17.32
Flux linkage
0.0–200.0%
0.0%
5.5.4 Space voltage vector control mode
The VFD also carries built-in space voltage vector control function. The space voltage vector control
mode can be used in cases where mediocre control precision is enough. In cases where a VFD
needs to drive multiple motors, it is also recommended to adopt space voltage vector control mode.
The VFD provides multiple kinds of V/F curve modes to meet different field needs. You can select
corresponding V/F curve or set the V/F curve as needed.
Suggestions:
 For the load featuring constant moment, such as conveyor belt which runs in straight line, as the
whole running process requires constant moment, it is recommended to adopt the straight line
V/F curve.
 For the load featuring decreasing moment, such as fan and water pumps, as there is a power
(square or cube) relation between its actual torque and speed, it is recommended to adopt the
V/F curve corresponding to the power of 1.3, 1.7 or 2.0.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive270 Series and is the answer not in the manual?

INVT Goodrive270 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive270 Series
CategoryWater Pump
LanguageEnglish

Related product manuals