Goodrive270 series VFD for fan and pump Basic operation guidelines
-148-
0: Invalid
1: PT100
2: PT1000
3: KTY84
Freezing protection
threshold
Low-temperature
pre-alarm threshold
-20.0°C –20.0°C
When the temperature is lower than the value of
this function code, the pre-alarm terminal
outputs a signal.
Freezing protection
frequency
Related parameter list:
The temperature is lower
than the freezing
protection threshold.
5.5.24 Condensation protection
When motors are in wet or cold environments, condensation can cause faults to the motors. This risk
can be eliminated by simply increasing the surface temperature of the motor during the work interval.
When the external condensation sensor detects intensive condensation, the VFD injects DC current
into the motor to raise the motor surface temperature to prevent condensation.
To implement the function: Set the S digital input terminal function to 91 to enable condensation
protection. If this terminal is enabled through external signal, the VFD sends DC current and
automatically stops the sending 40s later. If this function needs to be triggered again, re-enable this
function terminal. You can set P96.15 to adjust the DC current proportion.
Related parameter list:
Current of
triggering
condensation
protection