Parameter display
of motor 2
0: Display by motor type. In this mode, only
parameters related to the present motor type are
displayed.
1: Display all. In this mode, all the motor
parameters are displayed.
System inertia of
motor 2
P13 group––SM control
SM injected-current
decrease ratio
Used to set the reduction rate of the input
reactive current. When the active current of the
synchronous motor increases to some extent,
the input reactive current can be reduced to
improve the power factor of the motor.
Setting range: 0.0%–100.0% (of the motor rated
current)
Detection mode of
initial pole
0: No detection
1: High-frequency superposition
2: Pulse superposition
Pull-in current is the pole position orientation
current; pull-in current 1 is valid within the lower
limit of pull-in current switch-over frequency
threshold. If you need to increase the start
torque, increase the value of this function
parameter properly.
Setting range: 0.0%–100.0% (of the motor rated
current)
Pull-in current is the pole position orientation
current; pull-in current 2 is valid within the lower
limit of pull-in current switch-over frequency
threshold. You do not need to change the value
in most cases.
Setting range: 0.0%–100.0% (of the motor rated