Goodrive270 series VFD for fan and pump Troubleshooting
-279-
7.6.7 Motor stalls during ACC
Motor stalls during
ACC
Whether the ACC
time is too short?
If it is a VFD fault or
interference, contact our
company
Overcurrent
If it is a VFD fault or
interference, contact
our company
Whether parameter
autotuning is
performed?
Modify the torque
boost
Whether the
torque boost
is too high?
Whether a special
motor is used?
Reduce the inertia of
the load and
increase the capacity
of the VFD
Whether it is V/F
control?
Contact our
company
Whether the load
torque is too large?
Use larger cables, shorten the
wiring distance, adjust the voltage
drop of the output reactor, etc.
Whether the load
or inertia is too
large?
Increase the ACC
time
Check the voltage of the
terminals of the motor with a
multimeter. Whether the voltage
is within the defined range?
Reduce the torque of
the load and
increase the capacity
of the VFD
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive270 Series and is the answer not in the manual?

INVT Goodrive270 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive270 Series
CategoryWater Pump
LanguageEnglish

Related product manuals