Goodrive270 series VFD for fan and pump Function parameter list
-225-
Function
code
Name
Description
Default
Modify
3: Keep running
Thousands place: Stalling fault (same as that for
hundreds place)
P11.47
Fault protection
selection 17
0x0000–0x0003
Ones place: Dry pumping
0: Coast to stop
1: Stop according to the stop mode
2: Pre-alarm and run
3: Keep running
Tens place: Reserved
Hundreds place: Reserved
Thousands place: Reserved
0x0000
â—‹
P11.48
Fault protection
selection 18
Reserved
P11.49
Fault protection
selection 19
Reserved
P11.50
Fault protection
selection 20
Reserved
P11.51
Output frequency
selection for running
with pre-alarm
0x0000–0x0004
Ones place:
0: Run at the present running frequency
1: Run at the frequency set through keypad
2: Run at the upper limit frequency
3: Run at the lower limit frequency
4: Run at the backup frequency upon exceptions
0x0000
â—‹
P11.52
Backup frequency
upon exceptions
0.00 Hz–P00.03(Max. output frequency)
0
â—‹
P12 group––Parameters of motor 2
Function
code
Name
Description
Default
Modify
P12.00
Type of motor 2
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
â—Ž
P12.01
Rated power of
AM 2
0.1–3000.0kW
Depends
on model
â—Ž
P12.02
Rated frequency of
AM 2
0.01Hz–P00.03(Max. output frequency)
50.00Hz
â—Ž
P12.03
Rated speed of
1–60000rpm
Depends
â—Ž

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive270 Series and is the answer not in the manual?

INVT Goodrive270 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive270 Series
CategoryWater Pump
LanguageEnglish

Related product manuals