Goodrive270 series VFD for fan and pump Function parameter list
-199-
Output terminal
status at 2nd-last
fault
P08 group––Enhanced functions
For details, see P00.11 and P00.12.
The VFD has four groups of ACC/DEC time,
which can be selected by P05. The factory
default ACC/DEC time of the VFD is the first
group.
Setting range: 0.0–3600.0s
The function code is used to define the
reference frequency during jogging.
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
ACC time for jogging means the time needed for
the VFD to accelerate from 0Hz to the max.
output frequency (P00.03).
DEC time for jogging means the time needed for
the VFD to decelerate from the max. output
frequency (P00.03) to 0Hz.
Setting range: 0.0–3600.0s
When the set frequency is within the range of
jump frequency, the VFD runs at the boundary
of jump frequency.
The VFD can avoid mechanical resonance
points by setting jump frequencies. The VFD
supports the setting of three jump frequencies. If
the jump frequency points are set to 0, this
Jump frequency
amplitude 1
Jump frequency
amplitude 2