Goodrive270 series VFD for fan and pump Function parameter list
-256-
P92 group––Real-time clock and timer (available at use of LCD keypad)
Displaying month
and date
1–7
1–7 correspond to Monday–Sunday.
Displaying hour and
minute
00.00–23.59, HHMM
00.00 is the earliest hour and time of a day,
while 23.59 is the latest hour and time of a day.
Bit 0–Bit 6 correspond to Monday–Sunday.
Setting instances:
Monday: 0x01
Wednesday: 0x04
From Monday to Friday: 0x1F
From Saturday to Sunday: 0x60
VFD startup hour
and minute
P93 group––Fire control
0: Invalid
1: Fire mode 1
2: Fire mode 2
When P93.00=0, the fire mode is invalid, the
VFD runs in normal mode and it stops if
suffering a fault. When P93.00 is a non-zero
value and the fire signal is activated, the fire
mode is valid, and the VFD runs at the speed
specified by P93.01.
If fire mode 1 is selected, the VFD always runs