Goodrive270 series VFD for fan and pump Function parameter list
-211-
Low frequency
proportional gain
(Kp)
0.00–100.00
Low-frequency switching point: 5.00Hz,
high-frequency switching point: 10.00Hz
(P09.04 corresponds to high-frequency
parameter), and the middle is the linear
interpolation between these two points.
ACC/DEC time of
PID command
Low frequency
integral time (Ti)
Low frequency
differential time (Td)
Low frequency point
for PID parameter
switching
High frequency
point for PID
parameter switching
P10 group––Simple PLC and multi-step speed control
0: Stop after running once. The VFD stops
automatically after running for one cycle, and it
can be started only after receiving the running
command.
1: Keep running in the final value after running
for one cycle. The VFD keeps the running
frequency and direction of the last section after a
single cycle.
2: Cyclic running. The VFD enters the next cycle
after completing one cycle until receiving the
stop command.
Simple PLC
memory selection
0: Without memory at power failure
1: Memory at power-off. The PLC memories its