Goodrive270 series VFD for fan and pump Basic operation guidelines
-145-
Similar to manual polling, the pump cleaning function can be triggered only when the VFD is in
stopped state. To enable the pump cleaning function, set the terminal function to 86, enable the
terminal, and send a startup signal.
After the pump cleaning function is enabled, all water pumps are cleared in order. Then the VFD
automatically stops. During pump cleaning, you can terminate the pump cleaning by sending a stop
command. If you want to restart pump cleaning after pump cleaning is completed or terminated, you
need to send a stop command.
Figure 5-36 Pump cleaning logic
Related parameter list:
Function
code
Name
Description
Default
Modify
P96.20
Forward run
frequency for pump
cleaning
P00.05–P00.03
50Hz
â—Ž
P96.21
Reverse run
frequency for pump
cleaning
P00.05–P00.03
30Hz
â—Ž
P96.22
Forward run ACC
time for pump
cleaning
0–3600.0s
10.0s
â—‹
P96.23
Reverse run ACC
time for pump
cleaning
0–3600.0s
10.0s
â—‹
P96.24
Forward run
duration for pump
cleaning
1.0s–1000.0s
5.0s
â—‹
P96.25
Reverse run
duration for pump
cleaning
1.0s–1000.0s
5.0s
â—‹
P96.26
Forward/reverse
run interval for
1.0s–1000.0s
1.0s
â—‹

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive270 Series and is the answer not in the manual?

INVT Goodrive270 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive270 Series
CategoryWater Pump
LanguageEnglish

Related product manuals