Commissioning
Setting of mains data
Setting the voltage thresholds
6
108
EDBCSXA064 EN 3.2
Code Possible settings IMPORTANT
No. Designation Lenze/
{Appl.}
Selection
C0175 UG−Relais Fkt 1
Charge relay behaviour with
undervoltage (LU) in the DC bus.
107
1 Standard Relay switches as a function of
LU.
2 One Time Relay switches when LU is
exceeded for the first time and
remains on.
3 Fixed On Charging current limitation is
inactive.
l Relay is always switched on
and the charging resistors of
the axis module are thus
permanently jumpered.
l Setting for operation with
ECSxE power supply module.
6.5.2 Setting the voltage thresholds
Note!
All drive components in DC−bus connections must have the same thresholds!
Selection Mains voltage
Brake unit
LU message
(Undervoltage)
OU message
(Overvoltage)
C0173 Power supply module
[V AC]
Setting
[V DC]
Resetting
[V DC]
Setting
[V DC]
Resetting
[V DC]
0 230 yes/no 130 275 400 390
1 400 yes/no 285 430 800 790
2 400 ... 460 yes/no 328 473 800 790
3 480 no 342 487 800 785
4 480 yes 342 487 800 785
10 230 yes/no C0174 C0174 + 5 V 400 390
11 400 (Lenze setting) yes/no C0174 C0174 + 5 V 800 790
12 400 ... 460 yes/no C0174 C0174 + 5 V 800 790
13 480 no C0174 C0174 + 5 V 800 785
14 480 yes C0174 C0174 + 5 V 800 785
Code Possible settings IMPORTANT
No. Designation Lenze/
{Appl.}
Selection
C0174 UG min 60
Undervoltage threshold of DC
bus (LU)
107
15 {1 V} 342