EasyManuals Logo
Home>Lenze>Control Unit>ECS series

Lenze ECS series User Manual

Lenze ECS series
483 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #64 background imageLoading...
Page #64 background image
Electrical installation
Power terminals
Connection to the DC bus (+U
G
, −U
G
)
5
64
EDBCSXA064 EN 3.2
5.2.1 Connection to the DC bus (+U
G
, −U
G
)
Stop!
No device protection for DC bus voltage surges
In passive axis modules (without 24 V−supply), the charging circuit can be
overloaded through DC bus voltage surges.
Possible consequences:
ƒ Destruction of the device
Protective measures:
ƒ All axis modules in the DC−bus connection should be basically supplied with
a control voltage of 24 V.
ƒ If the total cable length is > 20 m, install an axis module or a capacitor module
directly at the power supply module.
ƒ Design the ±U
G
cables twisted and as short as possible. Ensure short−circuit−proof
routing!
ƒ Cable length (module « module) > 30 cm: install shielded ±U
G
cables.
Cable cross−section
Cable length
(module/
module)
Wire end ferrule Cable cross−section Tightening torque Stripping length
Up to 20 m
Without wire end
ferrule
6 mm
2
(AWG 10)
1.2 ... 1.5 Nm
(10.6 ... 13.3 lb−in)
5 mm for screw
connection
10 mm for spring
connection
With insulated wire end
ferrule
> 20 m
Without wire end
ferrule
10 mm
2
(AWG 8)
With insulated wire end
ferrule
Use pin−end connectors
for wiring!

Table of Contents

Other manuals for Lenze ECS series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze ECS series and is the answer not in the manual?

Lenze ECS series Specifications

General IconGeneral
BrandLenze
ModelECS series
CategoryControl Unit
LanguageEnglish

Related product manuals