Monitoring functions
Configuring monitoring functions
Motor temperature monitoring (OH3, OH7)
10
206
EDBCSXA064 EN 3.2
10.3.5 Motor temperature monitoring (OH3, OH7)
Stop!
The temperature sensor must only be connected to either X7 or X8, the other
input of the temperature sensor must be left open!
Note!
This monitoring function only applies to temperature sensors specified by
Lenze like the ones used on standard Lenze servo motors.
With regard to default setting, this monitoring is switched actively and is
actuated when no Lenze servo motor is used!
The motor temperature is monitored by means of a continuous KTY temperature sensor.
The motor temperature monitoring functions (OH3/OH7) respond when the set
temperature thresholds are exceeded.
Wire the KTY temperature sensor to the resolver cable at X7 ( 96) or the encoder cable
at X8 ( 97).
Fault message Monitoring function System variable
Possible response
TRIP Messag
e
Warnin
g
Off
053 OH3 Motor temperature
(fixed, 150 °C)
MCTRL_bMotorTempGreaterSet
Value_b
· ü ü
057 OH7 Motor temperature
(adjustable, C0121)
MCTRL_bMotorTempGreaterC0
121_b
ü · ü
· Default setting
üSetting possible
ƒ Adjustable warning threshold (OH7)
The warning threshold can be set under C0121
The reaction to exceeding the threshold can be set under C0584
ƒ Fixed warning threshold (OH3)
Threshold = 150 °C
The reaction to exceeding the threshold can be set under C0583
The hysteresis is 15 K, i.e. the switching value for the fixed warning threshold is 135 °C.
Monitoring with the adjustable threshold (OH7) is intended as an early warning stage prior
to the final disconnection of the controller by means of TRIP (OH3). In this way the process
can be influenced accordingly, so that a final disconnection of the controller at an
unfavourable moment is avoided. Furthermore, it is possible to activate e.g. additional
fans which would generate an unacceptable noise nuisance when operated continuously.
Code Possible settings IMPORTANT
No. Designation Lenze/
{Appl.}
Selection
C0121 OH7 limit 120
Threshold for motor temperature
monitoring
206
45 {1 °C} 150 Motor temperature > C0121 ð
fault message OH7 (C0584)

Table of Contents

Other manuals for Lenze ECS series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze ECS series and is the answer not in the manual?

Lenze ECS series Specifications

General IconGeneral
BrandLenze
ModelECS series
CategoryControl Unit
LanguageEnglish

Related product manuals