Technical data
Current characteristics
Device protection by current derating
3
47
EDBCSXA064 EN 3.2
3.3.2 Device protection by current derating
The maximum output current is limited. With output frequencies < 5 Hz the limitation
depends on the heatsink temperature.
0.75
1.00
0.57
0.38
0.67
0.00
1.00
0510
fout [Hz]
Iout
Imax
70 °C
90 °C
ECSXA024
Fig. 3−2 Current derating characteristics
Operation with switching frequency = 8 kHz (C0018 = 1).
l If the current exceeds the characteristic , the switching frequency is automatically
changed to 4 kHz (e.g. for higher torque in acceleration processes).
Operation with switching frequency = 4 kHz (C0018 = 0).
l The current limitation follows the characteristic .
l With output frequencies < 5 Hz and heatsink temperatures between 70 and 90 °C the
current limit is steplessly adjusted in the range .
Type
I
max
[A]
Switching frequency 8 kHz Switching frequency 4 kHz
f
out
> 5 Hz f
out
0 Hz f
out
> 5 Hz f
out
0 Hz
£ 70 °C
f
out
0 Hz
90 °C
ECSxA004 2.7 1.5 4.0 3.0 2.3
ECSxA008 5.3 3.0 8.0 6.0 4.6
ECSxA016 10.7 6.0 16.0 12.0 9.1
ECSxA032 21.3 12.1 32.0 24.0 18.1
ECSxA048 32.0 18.1 48.0 36.3 27.2
ECSxA064 42.7 24.2 64.0 48.0 36.3

Table of Contents

Other manuals for Lenze ECS series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze ECS series and is the answer not in the manual?

Lenze ECS series Specifications

General IconGeneral
BrandLenze
ModelECS series
CategoryControl Unit
LanguageEnglish

Related product manuals