AIF interface (X1) configuration
Reset node
XCAN Sync Tx transmission cycle
9
191
EDBCSXA064 EN 3.2
9.6.3 XCAN Sync Tx transmission cycle
The cycle time required for transmitting a sync telegram with the identifier set in C2368
can be configured via C2356/5:
Code Possible settings IMPORTANT
No. Designation Lenze/ap
pl.
Selection
C2356 Time settings for XCAN
(AIF interface X1)
188
1 XCAN times 0 0 {1 ms} 65000 XCAN boot−up time:
Delay time for initialisation
through the master after mains
connection.
2 XCAN times 0
XCAN1...3_OUT cycle times:
Factor for the task time to send
process data object.
0 = event−controlled
transmission
3 XCAN times 0
4 XCAN times 0
5 XCAN times 0 Delay time for initial
transmission of the process data
objects after the NMT status
changed to "Operational"
9.7 Reset node
Changes of the CAN baud rate, the node addresses and the identifiers are only accepted
after a node has been reset.
A reset node can be made by:
ƒ New mains connection
ƒ Reset node command by NMT command
ƒ Reset−node command via the SB AIF_IO_Management ( 255)

Table of Contents

Other manuals for Lenze ECS series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze ECS series and is the answer not in the manual?

Lenze ECS series Specifications

General IconGeneral
BrandLenze
ModelECS series
CategoryControl Unit
LanguageEnglish

Related product manuals