Monitoring functions
Configuring monitoring functions
Time−out monitoring for activated remote parameterisation
10
204
EDBCSXA064 EN 3.2
10.3.2 Time−out monitoring for activated remote parameterisation
If remote parameterisation is activated (gateway function ( 180)) and a timeout occurs,
the system error message CE5/CE15 is output.
The response to this can be configured via C0603/C2485.
Code Possible settings IMPORTANT
No. Designation Lenze/
{Appl.}
Selection
C0603 MONIT CE5 3
Fault response − gateway
function monitoring (CE5)
"Timeout" when remote
parameter setting (C0370) is
activated via interface X4 (CAN)
202
180
0 TRIP
2 Warning
3 Off
C2485 MONIT CE15 3
Fault response − gate function
monitoring (CE15)
"Timeout" when remote
parameterisation (C0370) is
activated via interface X14
(CAN−AUX)
202
180
0 TRIP
2 Warning
3 Off