System modules
CANaux1_IO (node number 34)
13
304
EDBCSXA064 EN 3.2
Codes
Code Possible settings IMPORTANT
No. Designation Lenze/
{Appl.}
Selection
C2456 CAN time settings for CAN bus
interface X14 (CAN−AUX)
163
1 CANa times 3000 0 {1 ms} 65000 CAN−AUX boot−up time:
Delay time after mains
connection for initialisation
through the master.
2 CANa times 0
CANaux2...3_OUT cycle times:
Factor for the task time to send
process data telegram.
0 = event−controlled
transmission
3 CANa times 0
4 CANa times 20 Delay time for initial
transmission of the process data
objects 2 and 3 after the CAN bus
changed to "Operational"
C2457 Monitoring time for
CANaux1...3_IN (CAN bus
interface X14)
202
1 CE monit time 3000 1 {1 ms} 65000 CE11 monitoring time
2 CE monit time 3000 CE12 monitoring time
3 CE monit time 3000 CE13 monitoring time
C2491 Process data input words
(hexadecimal) for CAN bus
interface X14
Hexadecimal value is bit−coded.
Read only
1 CANa IN bits 0 {1 hex} FFFF CANaux1_IN (bit 0 ... 15)
2 CANa IN bits CANaux1_IN (bit 16 ... 31)
3 CANa IN bits CANaux2_IN (bit 0 ... 15)
4 CANa IN bits CANaux2_IN (bit 16 ... 31)
5 CANa IN bits CANaux3_IN (bit 0 ... 15)
6 CANa IN bits CANaux3_IN (bit 16 ... 31)

Table of Contents

Other manuals for Lenze ECS series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze ECS series and is the answer not in the manual?

Lenze ECS series Specifications

General IconGeneral
BrandLenze
ModelECS series
CategoryControl Unit
LanguageEnglish

Related product manuals