System modules
DIGITAL_IO (node number 1)
Inputs_DIGITAL (digital inputs)
13
344
EDBCSXA064 EN 3.2
Codes
Code Possible settings IMPORTANT
No. Designation Lenze/
{Appl.}
Selection
C0114 Polarity of the digital inputs
129
1 DIGIN pol 0 HIGH level active X6/DI1 (DIGIN_bIn1_b)
2 DIGIN pol 0 HIGH level active X6/DI2 (DIGIN_bIn2_b)
3 DIGIN pol 0 HIGH level active X6/DI3 (DIGIN_bIn3_b)
4 DIGIN pol 0 HIGH level active X6/DI4 (DIGIN_bIn4_b)
0 HIGH level active
1 LOW level active
C0443 DIS: DIGIN
Signal status of the digital inputs
on X6 after consideration of the
polarity set under C0114.
Only display
343
0 {1} 255
Bit 0 DIGIN1 X6/DI1
Bit 1 DIGIN2 X6/DI2
Bit 2 DIGIN3 X6/DI3
Bit 3 DIGIN4 X6/DI4
Bit 4 DIGIN_safe_standstill X6/SI2
0: Pulse inhibit is active
1: Pulse inhibit is inactive
80
Bit 5 Free
Bit 6 DIGIN_CInh X6/SI1
0: Controller is inhibited (CINH)
1: Controller is enabled
80
Bit 7 Free
Terminal assignment
Terminal Function
X6 Digital inputs
X6/DI1
Digital input 1
(DigIn_bIn1_b)
freely assignable
X6/DI2
Digital input 2
(DigIn_bIn2_b)
X6/DI3
Digital input 3
(DigIn_bIn3_b)
X6/DI4
Digital input 4
(DigIn_bIn4_b)
X6
Connection of "Safe torque off"( 80)
X6/SI1 Input 1
LOW DIGIN_bCInh_b = TRUE
HIGH DIGIN_bCInh_b = FALSE
X6/SI2 Input 2
LOW DIGIN_b_safe_standstill_b = FALSE
HIGH DIGIN_b_safe_standstill_b = TRUE
X6/S24 Low−voltage supply