EasyManuals Logo

GE P642 User Manual

GE P642
592 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #193 background imageLoading...
Page #193 background image
2.1 RESISTANCE-EARTHED STAR WINDINGS
Most distribution systems use resistance-earthed systems to limit the fault current. Consider the diagram below,
which depicts an ear
th fault on the star winding of a resistance-earthed Dyn transformer (Dyn = Delta-Star with
star-point neutral connection).
V00669
Source
Current p.u.
(x full load)
Fault position from neutral
(Impedance earthing)
20% 100%
Winding not protected
Pickup
1.0
87
64
I
S
I
F
I
F
I
S
0.2
I
F
Figure 72: REF Protection for resistance-earthed systems
The v
alue of fault current (I
F
) depends on two factors:
The value of earthing resistance (which makes the fault path impedance negligible)
The fault point voltage (which is governed by the fault location).
Because the fault current (I
F
) is governed by the resistance, its value is directly proportional to the location of the
fault.
A restricted earth fault element is connected to measure I
F
directly. This provides very sensitive earth fault
protection. The overall differential protection is less sensitive, since it only measures the HV current I
S
. The value of
I
S
is limited by the number of faulty secondary turns in relation to the HV turns.
2.2 SOLIDLY-EARTHED STAR WINDINGS
Most transmission systems use solidly-earthed systems. Consider the diagram below, which depicts an earth fault
on the star winding of a solidly-ear
thed Dyn transformer.
V00670
Current p.u.
(x full load)
Source
Fault position from neutral
(Solid earthing)
20% 40% 60% 80% 100%
87
I
S
I
F
I
F
64
I
F
I
S
10
8
6
4
2
Figure 73: REF Protection for solidly earthed system
In this case, the fault curr
ent I
F
is dependent on:
The leakage reactance of the winding
The impedance in the fault path
The fault point voltage (which is governed by the fault location)
In this case, the value of fault current (I
F
) varies with the fault location in a complex manner.
A restricted earth fault element is connected to measure I
F
directly. This provides very sensitive earth fault
protection.
P64x Chapter 8 - Restricted Earth Fault Protection
P64x-TM-EN-1.3 169

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P642 and is the answer not in the manual?

GE P642 Specifications

General IconGeneral
BrandGE
ModelP642
CategoryRelays
LanguageEnglish

Related product manuals