4.6 CIRCUIT BREAKER FAIL PROTECTION
I< Pick-up 1.1 X setting +/- 5% or 20 mA, whichever is greater
I< Drop-off Setting +/- 5% or 20 mA, whichever is greater
Timers +/- 2% or 50 ms, whichever is greater
Reset time < 15 ms (fully offset current waveform considered)
P64x Chapter 21 - Technical Specifications
P64x-TM-EN-1.3 463