6 STANDARDS COMPLIANCE
Compliance with the European Commission Directive on EMC and LVD is demonstrated by self certification against
international standar
ds.
6.1 EMC COMPLIANCE: 2004/108/EC
Compliance with EN60255-26:2009 was used to establish conformity.
6.2 PRODUCT SAFETY: 2006/95/EC
Compliance with EN60255-27:2005 was used to establish conformity.
Pr
otective Class
IEC 60255-27: 2005 Class 1 (unless otherwise specified in equipment documentation). This equipment requires a
protective conductor (earth) to ensure user safety.
Installation category
IEC 60255-27: 2005 Overvoltage Category 3. Equipment in this category is qualification tested at 5kV peak, 1.2/50
mS, 500 Ohms, 0.5 J, between all supply circuits and earth and also between independent circuits.
Environment
IEC 60255-27: 2005, IEC 60255-26:2009. The equipment is intended for indoor use only. If it is required for use in an
outdoor environment, it must be mounted in a cabinet with the appropriate degree of ingress protection.
6.3 R&TTE COMPLIANCE
Radio and Telecommunications Terminal Equipment (R&TTE) directive 99/5/EC.
Conformity is demonstrated by compliance to both the EMC dir
ective and the Low Voltage directive, to zero volts.
6.4 UL/CUL COMPLIANCE
If marked with this logo, the product is compliant with the requirements of the Canadian and USA Underwriters
Laboratories.
The r
elevant UL file number and ID is shown on the equipment.
6.5 ATEX COMPLIANCE
If marked with the logo, the equipment is compliant with article 192 of European directive 94/9/EC. It is approved
for operation outside an A
TEX hazardous area. It is however approved for connection to Increased Safety, "Ex e",
motors with rated ATEX protection, equipment category 2, to ensure their safe operation in gas zones 1 and 2
hazardous areas.
Equipment with this marking is not itself suitable for operation within a potentially explosive
atmospher
e.
Chapter 2 - Safety Information P64x
24 P64x-TM-EN-1.3