Goodrive270 series VFD for fan and pump Function parameter list
-240-
P23.01 setting range: 0.000–10.000s
P23.02 setting range: 0.00Hz–P23.05
P23.03 setting range: 0.0–200.0
P23.04 setting range: 0.000–10.000s
P23.05 setting range: P23.02–P00.03 (Max.
output frequency)
0–8 (corresponding to 0–2
8
/10ms)
Electromotive slip
compensation
coefficient of vector
control
Slip compensation coefficient is used to adjust
the slip frequency of the vector control and
improve the speed control accuracy of the
system. Adjusting the parameter properly can
control the speed steady-state error.
Setting range: 50–200%
Braking slip
compensation
coefficient of vector
control
Current-loop
proportional
coefficient P
Note:
1. The two function codes impact the dynamic
response speed and control accuracy of the
system. Generally, you do not need to
modify the two function codes.
2. Applicable to SVC mode 0 (P00.00=0)
3. The values of the two function codes are
updated automatically after SM parameter
autotuning is completed.
Setting range: 0–65535
Current-loop
integral coefficient I
Speed-loop
differential gain
High-frequency
current-loop
proportional
coefficient
In the vector control mode (P00.00=3), when the
frequency is lower than the current-loop
high-frequency switching threshold (P23.14), the
current-loop PI parameters are P23.09 and
P23.10; and when the frequency is higher than
the current-loop high-frequency switching
threshold, the current-loop PI parameters are
P23.12 and P23.13.
P23.12 setting range: 0–65535
P23.13 setting range: 0–65535
High-frequency
current-loop integral
coefficient
Current-loop
high-frequency
switching threshold