LX12 Baud Rate
This parameter sets the external serial communication baud rate at port X4A. This port
connects to the operator or can be used for diagnostics with Combivis or the mobile app.
When the operator is connected, the baud rate is auto negotiated. When communication
is lost, the baud rate will auto reset to 38400 bps. The communication is DIN 66019 II
standard.
LX13 Speed Following Error
This parameter can be used to trigger a drive warning/error if the actual motor speed
deviates from the contract speed or command speed by more than the window defined in
parameter LX14.
This function only works in closed loop speed control mode (i.e., LC01 = Closed Loop
FOC, Closed Loop Analog Pre-torque, Closed Loop Digital Pre-torque, Closed Loop
Synthetic Pre-torque).
On with error % contract speed
On with error % command speed
Table 25. LX13 Speed following error settings
Speed following error drops output
drive.
On with Error % of
Contract Speed
deviates from contract speed by more than the window
defined in LX14.