Parameter Name / value range / [default seng] Info
0x2342:002
(P511.02)
Acve PROFIBUS sengs: Acve baud rate
(PROFIBUS diag.: Acve baud rate)
Read only
Display of the acve baud rate.
0 12 Mbps
1 6 Mbps
2 3 Mbps
3 1.5 Mbps
4 500 kbps
5 187.5 kbps
6 93.75 kbps
7 45.45 kbps
8 19.2 kbps
9 9.6 kbps
15 Search Automac baud rate detecon acve.
0x2342:003
(P511.03)
Acve PROFIBUS sengs: Watchdog me
(PROFIBUS diag.: Watchdog me)
Read only
Display of the watchdog monitoring me specied by the master.
Monitoring starts with the arrival of the rst telegram.
When a value of "0" is displayed, the monitoring funcon is deacva-
ted.
A change in the watchdog monitoring me in the master is eecve
immediately.
0x2348:001
(P516.01)
PROFIBUS Status: Bus status
(PROFIBUS Status: Bus status)
Read only
Display of the current DP state machine state (DP-STATE).
0 WAIT_PRM Aer the run-up, the inverter (slave) is waing for parameter data
(CHK_PRM) from the master. All other frame types are not processed.
Exchanging user data with the master is not possible yet.
1 WAIT_CFG The inverter (slave) is waing for conguraon data (CHK_CFG) from the
master that dene the structure of the cyclic frames.
2 DATA_EXCH Parameter and conguraon data have been received and accepted by
the inverter (slave). The inverter is in the "Data Exchange" state. It is now
possible to exchange user data with the master.
0x2348:002
(P516.02)
PROFIBUS Status: Watchdog status
(PROFIBUS Status: Watchdog status)
Read only
Display of the current state of the watchdog state machine (WD-STATE).
0 BAUD_SEARCH The inverter (slave) is able to detect the baud rate automacally.
1 BAUD_CONTROL Aer detecng the correct baud rate, the inverter (slave) status changes
to BAUD_CONTROL, and the baud rate is monitored.
2 DP_CONTROL The DP_CONTROL state serves to the response monitoring of the master.
Diagnoscs and fault eliminaon
Diagnoscs parameter
Network diagnoscs
123