Parameter Name / value range / [default seng] Info
0x2342:002
(P511.02)
Acve PROFIBUS sengs: Acve baud rate
(PROFIBUS diag.: Acve baud rate)
•
Read only
Display of the acve baud rate.
0 12 Mbps
1 6 Mbps
2 3 Mbps
3 1.5 Mbps
4 500 kbps
5 187.5 kbps
6 93.75 kbps
7 45.45 kbps
8 19.2 kbps
9 9.6 kbps
15 Search Automac baud rate detecon acve.
0x2342:003
(P511.03)
Acve PROFIBUS sengs: Watchdog me
(PROFIBUS diag.: Watchdog me)
•
Read only
Display of the watchdog monitoring me specied by the master.
•
Monitoring starts with the arrival of the rst telegram.
•
When a value of "0" is displayed, the monitoring funcon is deacva-
ted.
•
A change in the watchdog monitoring me in the master is eecve
immediately.
0x2348:001
(P516.01)
PROFIBUS Status: Bus status
(PROFIBUS Status: Bus status)
•
Read only
Display of the current DP state machine state (DP-STATE).
0 WAIT_PRM Aer the run-up, the inverter (slave) is waing for parameter data
(CHK_PRM) from the master. All other frame types are not processed.
Exchanging user data with the master is not possible yet.
1 WAIT_CFG The inverter (slave) is waing for conguraon data (CHK_CFG) from the
master that dene the structure of the cyclic frames.
2 DATA_EXCH Parameter and conguraon data have been received and accepted by
the inverter (slave). The inverter is in the "Data Exchange" state. It is now
possible to exchange user data with the master.
0x2348:002
(P516.02)
PROFIBUS Status: Watchdog status
(PROFIBUS Status: Watchdog status)
•
Read only
Display of the current state of the watchdog state machine (WD-STATE).
0 BAUD_SEARCH The inverter (slave) is able to detect the baud rate automacally.
1 BAUD_CONTROL Aer detecng the correct baud rate, the inverter (slave) status changes
to BAUD_CONTROL, and the baud rate is monitored.
2 DP_CONTROL The DP_CONTROL state serves to the response monitoring of the master.
Diagnoscs and fault eliminaon
Diagnoscs parameter
Network diagnoscs
123