Parameter Name / value range / [default seng] Info
0x2639:002
(P440.02)
Analog output 1: Funcon
(Analog output 1: AO1 funcon)
Selecon of the signal to be shown at analog output 1.
0 Not acve No output signal.
1 Output frequency Actual output frequency (resoluon: 0.1 Hz).
2 Frequency setpoint Actual frequency setpoint (resoluon: 0.1 Hz).
3 Analog input 1 Input signal of analog input 1 (resoluon: 0.1 %).
4 Analog input 2 Input signal of analog input 2 (resoluon: 0.1 %).
5 Motor current Actual motor current (resoluon: 0.1 A).
6 Output power Actual output power (resoluon: 0.001 kW).
7 Torque actual value (from version 03.00) Torque actual value (resoluon: 0.1 %).
100 % ≡ permissible maximum torque 0x6072 (P326.00)
10 Sequencer controlled (from version 03.00) Voltage value which has been set for the currently executed sequencer
segment (resoluon: 0.01 V).
4Sequencer ^ 504
20 NetWordIN3 Actual value of the NetWordIN3 data word (resoluon: 0.1 %).
4Further process data ^ 251
21 NetWordIN4 Actual value of the NetWordIN4 data word (resoluon: 0.1 %).
4Further process data ^ 251
201 Internal value (from version 05.00) Internal values of the manufacturer.
202 Internal value (from version 05.00)
203 Internal value (from version 05.00)
204 Internal value (from version 05.00)
205 Internal value (from version 05.00)
206 Internal value (from version 05.00)
0x2639:003
(P440.03)
Analog output 1: Min. signal
(Analog output 1: AO1 min. signal)
-2147483648 ... [0] ... 2147483647
Denion of the signal value that corresponds to the minimum value at
analog output 1.
Example: conguraon of analog output 1 as a 4 ... 20 mA current loop:
output current 4 mA ≡ 0x2639:003
0x2639:004
(P440.04)
Analog output 1: Max. signal
(Analog output 1: AO1 max. signal)
-2147483648 ... [1000] ... 2147483647
Denion of the signal value that corresponds to the maximum value at
analog output 1.
Example: conguraon of analog output 1 as a 4 ... 20 mA current loop:
output current 20 mA ≡ 0x2639:004
0x4008:003
(P590.03)
Process input words: NetWordIN3
(NetWordINx: NetWordIN3)
0.0 ... [0.0] ... 100.0 %
Mappable data word for oponal control of an analog output via net-
work.
Assignment of the analog outputs:
Analog output 1: 0x2639:002 (P440.02) = "NetWordIN3 [20]"
Analog output 2: 0x263A:002 (P441.02) = "NetWordIN3 [20]"
0x4008:004
(P590.04)
Process input words: NetWordIN4
(NetWordINx: NetWordIN4)
0.0 ... [0.0] ... 100.0 %
Mappable data word for oponal control of an analog output via net-
work.
Assignment of the analog outputs:
Analog output 1: 0x2639:002 (P440.02) = "NetWordIN4 [21]"
Analog output 2: 0x263A:002 (P441.02) = "NetWordIN4 [21]"
Flexible I/O conguraon
Conguraon of analog outputs
Analog output 1