7.1 Mains voltage
The rated mains voltage set for the inverter has an impact on the operang range of the inver-
ter.
Details
By default, the rated mains voltage in 0x2540:001 (P208.01) is set according to the product
code of the inverter.
Check the seng of the rated mains voltage in 0x2540:001 (P208.01). Ensure
that it matches the actual mains voltage applied!
Region Inverter Product code
0x2000:001 (P190.01)
Rated mains voltage
Default seng Possible sengs
EU i500, 230 V, 1-phase i5xAExxxBxxxx0xxxx 230 Ve [0] 230 Ve [0]
US i500, 230 V, 1-phase i5xAExxxBxxxx1xxxx 230 Ve [0] 230 Ve [0]
EU i500, 230 V, 1/3-phase i5xAExxxDxxxx0xxxx 230 Ve [0] 230 Ve [0]
US i500, 230 V, 1/3-phase i5xAExxxDxxxx1xxxx 230 Ve [0] 230 Ve [0]
EU i500, 400 V, 3-phase i5xAExxxFxxxx0xxxx 400 Ve [1] 400 Ve [1], 480 Ve [2]
US i500, 480 V, 3-phase i5xAExxxFxxxx1xxxx 480 Ve [2] 400 Ve [1], 480 Ve [2]
EU i500, 120 V, 1-phase i5xAExxxAxxxx0xxxx 120 Ve [3] 120 Ve [3]
US i500, 120 V, 1-phase i5xAExxxAxxxx1xxxx 120 Ve [3] 120 Ve [3]
Notes regarding the table:
•
The inverter types 400/480 V can be used with dierent mains voltages. For seng the
internal limit values, the rated mains voltage can be set in 0x2540:001 (P208.01) by the
user.
•
The inverter types 120 V are designed for a 1-phase 120-V mains voltage and 3-phase 230-
V three-phase AC motors. These inverters have an internal DC bus similar to the 230-V
inverters. The voltage thresholds correspond to the ones of the 230-V inverters.
•
If the inverter is reset to the delivery status, the rated mains voltage is also reset to the
default seng listed in the table according to the product code.
The following results from the rated mains voltage set:
•
the error threshold for monitoring the DC-bus voltage and
•
the voltage threshold for braking operaon ("brake chopper threshold").
Monitoring of the DC-bus voltage
•
The warning thresholds for monitoring are adjustable.
•
The error thresholds and reset thresholds for monitoring result from the rated mains volt-
age set:
Rated mains volt-
age
Undervoltage thresholds Overvoltage thresholds
Warning threshold Error threshold Reset threshold Warning threshold Error threshold Reset threshold
Seng in
0x2540:001
(P208.01)
Seng in
0x2540:002
(P208.02)
Display in
0x2540:003
(P208.03)
Display in
0x2540:004
(P208.04)
Seng in
0x2540:005
(P208.05)
Display in
0x2540:006
(P208.06)
Display in
0x2540:007
(P208.07)
•
If the DC-bus voltage of the inverter falls below the undervoltage error threshold, the
"Trouble" response is triggered.
•
Without external 24-V supply: Motor behaves according to 0x2838:002 (P203.02).
•
With external 24-V supply: At undervoltage, motor behaves according to disturbance
response.
•
If the DC-bus voltage of the inverter exceeds the overvoltage error threshold, the "Fault"
response is triggered.
The motor does not restart automacally aer the overvoltage monitoring func-
on has been acvated.
Basic seng
Mains voltage
144