8.7.2 Motor temperature monitoring
In order to record and monitor the motor temperature, a PTC thermistor (single sensor
according to DIN 44081 or triple sensor according to DIN 44082) or thermal contact (normally-
closed contact) can be connected to the terminals T1 and T2. This measure helps to prevent
the motor from being destroyed by overheang.
Precondions
The inverter can only evaluate one PTC thermistor! Do not connect several PTC thermistors
in series or parallel.
If several motors are actuated on one inverter, thermal contacts (NC contacts) connected
in series are to be used.
To achieve full motor protecon, an addional temperature monitoring funcon with a
separate evaluaon must be installed.
By default, a wire jumper is installed between terminals X109/T1 and X109/T2, which must
be removed when the PTC thermistor or thermal contact is connected.
Details
If 1.6 kΩ < R < 4 kΩ at terminals X109/T1 and X109/T2, the monitoring funcon will be acva-
ted; see funconal test below.
If the monitoring funcon is acvated, the response set in 0x2D49:002 (P309.02) will be
eected.
The seng 0x2D49:002 (P309.02) = 0 deacvates the monitoring funcon.
If a suitable motor temperature sensor is connected to the terminals X109/T1
and X109/T2 and the response in 0x2D49:002 (P309.02) is set to "Fault [3]", the
response of the motor overload monitoring may be set other than "Fault [3]" in
0x2D4B:003 (P308.03).
4Motor overload monitoring (i²*t) ^ 215
Funconal test
Connect a xed resistor to the PTC input:
R > 4 kΩ : the monitoring funcon must be acvated.
R < 1 kΩ : the monitoring funcon must not be acvated.
Parameter Name / value range / [default seng] Info
0x2D49:002
(P309.02)
Motor temperature monitoring: Response
(Mot.temp.monit.: Response)
For further possible sengs, see parameter
0x2D45:001 (P310.01). ^ 223
Selecon of the response to the triggering of the motor temperature
monitoring.
Associated error code:
17168 | 0x4310 - Motor overtemperature error
3 Fault
Motor control
Motor protecon
Motor temperature monitoring
219