Parameter Name / value range / [default seng] Info
0x2859:008
(P515.08)
Modbus TCP/IP monitoring: Fault reacon by me-out
Master
(MBTCP monitoring: React t-out mast)
•
From version 04.00
•
For further possible sengs, see parameter
0x2D45:001 (P310.01). ^ 223
Selecon of the response if within the me set in 0x23B6:001 (P514.01)
no valid message has arrived at the Modbus master.
Associated error code:
•
33046 | 0x8116 - Modbus TCP master me-out
3 Fault
0x2859:009
(P515.09)
Modbus TCP/IP monitoring: Fault reacon by me-out
Keep alive
(MBTCP monitoring: Reac t-out kp-al)
•
From version 04.00
•
For further possible sengs, see parameter
0x2D45:001 (P310.01). ^ 223
Selecon of the response if within the me set in 0x23B6:002
(P514.02)no valid message has been wrien into the keep alive register.
Associated error code:
•
33047 | 0x8117 - Modbus TCP Keep Alive me-out
3 Fault
9.8.4 LED status displays
Informaon on the CIP status can be obtained quickly via the "MS" and "NS" LED displays on
the front of the inverter. In addion, the LEDs at the RJ45 sockets indicate the Ethernet con-
necon status.
The meaning of the "MS" and "NS" LEDs can be obtained from the following two tables.
LED "MS" (green/red) Module status Status/meaning
o Nonexistent The network opon is not supplied with voltage.
On (green)
Operaonal The network opon works correctly.
Blinking green
Standby The network opon is not congured completely or the conguraon is incorrect.
Blinking red
Major recoverable
fault
The network opon contains a correctable error.
on (red)
Major unrecoverable
fault
The network opon contains a non-correctable error.
Blinking green/red
Device self tesng The network opon executes a self-test.
LED "NS" (green/red) Network status Status/meaning
o No IP address The network opon is not supplied with voltage or has not received an IP address yet.
On (green)
Connected The network opon works correctly an has established a connecon to the master.
Blinking green
No connecons The network opon
•
works correctly,
•
has been assigned to an IP address,
•
has not been implemented into the network yet by the master.
Blinking red
Connecon meout A me-out has occurred.
on (red)
Duplicate IP The network opon cannot access the network (IP address conict).
Blinking green/red
Device self tesng The network opon executes a self-test.
Status displays at the RJ45 sockets
The LEDs at the RJ45 sockets indicate the connecon status to the network:
LED "Link" (green) Status/meaning
o No connecon to the network.
on
A physical connecon to the network is available.
LED "Acvity" (yellow) Status/meaning
o No data transfer.
on or ickers
Data is exchanged via the network.
Conguring the network
Modbus TCP
LED status displays
352