6.2.4.2 Modbus diagnoscs
The following parameters serve to diagnose the Modbus interface and communicaon via
Modbus.
Precondions
Control unit (CU) of the inverter is provided with Modbus.
Parameter Name / value range / [default seng] Info
0x2322:001
(P511.01)
Acve Modbus sengs: Acve node ID
(Modbus diag.: Acve node ID)
Read only
Display of the acve node address.
0x2322:002
(P511.02)
Acve Modbus sengs: Acve baud rate
(Modbus diag.: Acve baud rate)
Read only
For the meaning of the display see parameter
0x2321:002 (P510.02). ^ 283
Display of the acve baud rate.
0x2322:003
(P511.03)
Acve Modbus sengs: Data format
(Modbus diag.: Data format)
Read only
For the meaning of the display see parameter
0x2321:003 (P510.03). ^ 283
Display of the acve data format.
0x232A:001
(P580.01)
Modbus stascs: Messages received
(Modbus stasc: Mess. received)
Read only
Display of the total number of messages received.
This counter counts both valid and invalid messages.
Aer the maximum value has been reached, the counter starts again
"0".
0x232A:002
(P580.02)
Modbus stascs: Valid messages received
(Modbus stasc: Val. mess. rec.)
Read only
Display of the number of valid messages received.
Aer the maximum value has been reached, the counter starts again
"0".
0x232A:003
(P580.03)
Modbus stascs: Messages with excepons
(Modbus stasc: Mess. w. exc.)
Read only
Display of the number of messages with excepons that have been
received.
Aer the maximum value has been reached, the counter starts again
"0".
0x232A:004
(P580.04)
Modbus stascs: Messages with errors
(Modbus stasc: Mess. w. errors)
Read only
Display of the number of messages received with a faulty data integrity
(parity, CRC).
Aer the maximum value has been reached, the counter starts again
"0".
0x232A:005
(P580.05)
Modbus stascs: Messages sent
(Modbus stasc: Messages sent)
Read only
Display of the total number of messages sent.
Aer the maximum value has been reached, the counter starts again
"0".
Related topics
4Modbus RTU ^ 282
6.2.4.3 PROFIBUS diagnoscs
The following parameters serve to diagnose the PROFIBUS interface and communicaon via
PROFIBUS.
Precondions
Control unit (CU) of the inverter is provided with PROFIBUS.
Parameter Name / value range / [default seng] Info
0x2342:001
(P511.01)
Acve PROFIBUS sengs: Acve staon address
(PROFIBUS diag.: Act.staon addr)
Read only
Display of the acve staon address.
Diagnoscs and fault eliminaon
Diagnoscs parameter
Network diagnoscs
122